Angelor (Jiangsu) Intelligent Electric co.,LTD.

Position:首页 > Products > Power cable accessories > Power cable terminations > Premolded cable terminations

66~110kV Porcelain insulation outdoor termination

Product Descriptions

● The product uses high-strength porcelain sleeve which has the advantage of high mechanical strength, good stability, no aging, especially suitable for coastal and natural environment harsh areas.

● The product adopts the structure of big and small umbrella skirt, and the experiment has proved that this structure has excellent pollution resistance.

● It has a good sealing performance to prevent flooding, oil leakage and other possible defects.

● Porcelain insulator comes in two sizes. One specification is 1280mm high and 3150mm creepage distance, which is suitable for Ⅲ-level dirty areas. The other specification is 1400mm high and the creepage distance is 3906mm, which is suitable for Ⅳ-level dirty areas.

Product introduction: 110kV porcelain sleeve outdoor terminal product introduction.pdf

Structure diagram: 110kV porcelain sleeve outdoor terminal structure diagram.pdf


Contact us

Product Details

Technical Specifications
Area Of Application
Applicable cable cross-sections:240~1600 mm2
Max.system voltage:126 kV
System rated frequency:50 Hz
Elevation:≤2000 m
Operation temperature;-55 ℃~45 ℃
Cable Shield StyleTape/wire/corrugated Al
Design Data
Height1980±50 mm
Weight(excluding cable)230 kg / 507.06 lbs
Composite insulatorBending moment resistance≥2000 kN
Internal withstand pressure2.5 MPa
Breakdown pressure2.8 MPa
Filling fluid(material)PIB/Gel
Creepage distance≥4050 mm
Permissible horizontal pull of connecting wire≥2 kN
Storage temperature0 ℃~35 ℃
Installation temperature5 ℃~35 ℃
Electrical Test
Electrical Type Test (IEC 60840)
Heating cycle voltage152 kV
Partial discharge test at ambient and elevated temperaturesNo detctable discharge exceeding the declared sensitivity (114kV, 3.6pC)
Lighting impulse voltage 1.2 ㎲/50 ㎲650 kV
Electrical Routine Test (IEC 60840)
AC withstand voltage190 kV
Partial discharge testNo detctable discharge exceeding the declared sensitivity (114kV, 3.6pC)



Product Recommendation

Free Quote Inquiry

Fill out the form below and we’ll get in touch within 1 business day.

Submit

Copyright © 2025 Angelor (Jiangsu) Intelligent Electric co.,LTD.

Privacy PolicyTerms and Conditions