● Be made of imported liquid silicone rubber.
● Be divided into 3 cores, 4 cores, 5 cores.
● Be widely used in the terminal treatment.
● With features of waterproof, moisture proof, excellent capability and easy installation.
● Cable shield type: tape/wire.
Product introduction: 1kV Cold Shrink Terminal Product Introduction.pdf
Structure diagram: 1kV cold shrink four-core terminal structure diagram.pdf
Contact us| Technical Specifications | |
| Area Of Application | |
| Applicable cable cross-sections | 25 ~ 630 mm2 |
| Max.system voltage | 17.5 kV |
| System rated frequency | 50 Hz |
| Elevation | ≤ 2000 m |
| Operation temperature | -55 ℃~45 ℃ |
| Number of cores | 1 core, 3 cores |
| Cable Shield Style | Tape/wire |
| Design Data | |
| Height | 840 mm |
| Weight of insulator | 0.5 ~ 1kg |
| Material of insulator | Liquid silicone rubber |
| Creepage distance | 440 mm |
| Storage temperature | 0 ℃ ~ 35 ℃ |
| Installation temperature | 5 ℃ ~ 35 ℃ |
| Electrical Test (IEC 60502.4) | |
| AC voltage (5 mins) | 39 kV |
| AC voltage (wet, 1 min) | 35 kV |
| Partial discharge test at ambient and elevated temperature | 15 kV(≤ 2.8 pC) |
| Impulse ( 95 ℃ ~ 100 ℃, 10 impulses of each polarity) | 95 kV |
| AC voltage (after impulse, 15 mins) | 22 kV |
| Humidity | 11 kV, 300h |
| Salt fog | 11 kV, 1000h |